Holly Lane, Barwell, Leicestershire, LE9 8BT
Enquiries@HiskinsElectrical.co.uk
| Quote Number | QUO-3434 |
| Quote Date | 25th May 2024 |
| Valid Until | 24th June 2024 |
| Total | £3,290.00 |
Saw Mill, Thurlaston, Enderby Rd, Thurlaston, Leicester LE9 7TF
| Hrs/Qty | Service | Rate/Price | Sub Total |
|---|---|---|---|
| 1 | Observation 4 DB1 Circuits 4L3 Incorrect selection of circuit protective device for circuit supplying lighting. (411.3.2; 411.4; 411.5; 411.6; Sections 432, 433) (433.1; 533.2.1) |
£60.00 | £60.00 |
| 1 | Observation 5 DB1 Circuit 4L2, unidentified end point. (514.8.1; 514.9.1) |
£160.00 | £160.00 |
| 1 | Observation 6 DB1 Circuit 4L3, no residual current protection. (411.4.204; 411.5.2; 531.2) (411.3.3; 415.1) |
£150.00 | £150.00 |
| 1 | Observation 8 Junction box in press room has no cover and singularly insulated cables are exposed. (526.8) (526.5) (522.8.5) |
£60.00 | £60.00 |
| 1 | Observatin 9 Incorrect selection of circuit protective device for circuit supplying lighting in press room (411.3.2; 411.4; 411.5; 411.6; Sections 432, 433) (433.1; 533.2.1) |
£60.00 | £60.00 |
| 1 | Observation 10 DB1a supplied directly from incoming supply without overload protection. (411.3.2; 411.4; 411.5; 411.6; Sections 432, 433) |
£350.00 | £350.00 |
| 1 | Observation 11, 14 and 21 IP rating of DB1 is insufficient. (416.2) |
£80.00 | £80.00 |
| 1 | Observation 17 DB2 Circuit 3L1, no residual current protection. (411.4.204; 411.5.2; 531.2) (411.3.3; 415.1) |
£150.00 | £150.00 |
| 1 | Observation 18 DB2 Circuit 3L2, no residual current protection. (411.4.204; 411.5.2; 531.2) (411.3.3; 415.1) |
£150.00 | £150.00 |
| 1 | Observation 19 DB2 Circuit 7L1, no residual current protection. (411.4.204; 411.5.2; 531.2) (411.3.3; 415.1) |
£150.00 | £150.00 |
| 1 | Observation 20 DB2 Circuit 9L1-9L3, additional cables attached to circuit. (514.8.1; 514.9.1) |
£160.00 | £160.00 |
| 1 | Observation 24 DB2 Circuit 3L1, socket with insufficient IP rating. (416.2) |
£90.00 | £90.00 |
| 1 | Observation 26 Db1 Circuit 3L1 has additional cables attached. (514.8.1; 514.9.1) |
£160.00 | £160.00 |
| 1 | Observation 27 DB1 Circuit 1L1-1L3, Selection of protective device for installed cables is unsuitable. (411.3.2; 411.4; 411.5; 411.6; Sections 432, 433) (Section 523) (433.1; 533.2.1) |
£160.00 | £160.00 |
| 1 | Observation 27a DB1 Circuit 6L1-6L3, Selection of protective device for installed cables is unsuitable. (411.3.2; 411.4; 411.5; 411.6; Sections 432, 433) (Section 523) (433.1; 533.2.1) |
£160.00 | £160.00 |
| 1 | Observation 28 DB1 Circuit 11L1-11L3, additional cables attached. (514.8.1; 514.9.1) |
£160.00 | £160.00 |
| 1 | Observation 29 DB1 Circuit 12L1-12L3, Selection of protective device for installed cables is unsuitable. (411.3.2; 411.4; 411.5; 411.6; Sections 432, 433) (Section 523) (433.1; 533.2.1) |
£150.00 | £150.00 |
| 1 | Observation 31 DB2 Circuit 4L3, R1+R2 is higher than permitted by BSEN7671. (411.4.201) (411 .3.2.2) |
£80.00 | £80.00 |
| 1 | Observation 32 DB2 Circuit 12L1-12L3, Selection of protective device for installed cables is unsuitable. (411.3.2; 411.4; 411.5; 411.6; Sections 432, 433) (Section 523) (433.1; 533.2.1) |
£150.00 | £150.00 |
| 1 | Observation 33 DB1a Circuit 1L1-1L3, Selection of protective device for installed cables is unsuitable. (411.3.2; 411.4; 411.5; 411.6; Sections 432, 433) (Section 523) (433.1; 533.2.1) |
£150.00 | £150.00 |
| 1 | Observation 34 DB1a Circuit 1L1-1L3, selection of cable (SY Cable) used in this circuit does not comply with BSEN7671. (Section 523) |
£160.00 | £160.00 |
| 1 | Observation 35 DB1a Circuit 2L1-2L3, selection of cable (SY Cable) used in this circuit does not comply with BSEN7671. (Section 523) |
£160.00 | £160.00 |
| 1 | Observation 36 DB2a Circuit 1L1-1L3, co-ordination between circuit protective conductor and cable sizes may not comply with BSEN7671, further testing required with isolation of circuit and shut down of attached machinery. (411.3.2; 411.4; 411.5; 411.6; Sections 432, 433) (Section 523) (433.1; 533.2.1) |
£80.00 | £80.00 |
| 1 | Observation 37 Light switch at entrance to factory is not attached to back box, live connections exposed. (526.8) (526.5) (522.8.5) |
£0.00 | £0.00 |
| 1 | Observation 38 Light in bathroom is not correctly closed, live connections exposed. (526.8) (526.5) (522.8.5) |
£100.00 | £100.00 |
| Sub Total | £3,290.00 |