During my visit to you property today the following observations were made, as discussed despite these observation being about the current installation not meeting some of the current regulations there is no lawful obligation on your part to bring the installation up to current standards.

Hrs/Qty Service Rate/PriceSub Total
1 Upgrade of current fuse board to current 18th edition regulations Consumer Unit

1. Current fuse board does not provide RCD protection of circuits.
2. Bonding of extraneous conductive parts both not present for one service and under sized for another.
3. Circuits not separated adequately.

£500.00£500.00
1 Upgrade of bonding to extraneous conductive parts and installation of bonding where missing

The purpose of earthing is to provide a path for electric fault current to flow safely to earth to enable the circuit breaker or fuse to operate. Bonding is the connection of the incoming metal gas and water pipes to the main installation earthing terminal and is vital for your protection from electric shock.

£150.00£150.00
1 Upgrade of meter tails

Your current meter tails are 16mm, when a new consumer unit is installed it is require by current regulations to upgrade these to 25mm.

£60.00£60.00
1 Separation of circuits

The installation of a new consumer unit will allow for the separation of some of the existing circuits how ever without further work within the property it self, not all circuits will be separated. The installation of the new consumer unit will be a huge leap forward in bringing the electrical safety of the property closes to current regulations.

£0.00£0.00